Optimized &industry-ready solutions

Five MAGIC models — from a 10 g wall-mounted unit to a 100 g stainless-steel version — all using S-Type aerosol fire extinguishing technology.

DIN-Rail Type 30GDIN-Rail Type 30G - second view
PRODUCT 01

DIN-Rail Type

Model 30G — A compact unit for electrical cabinets, distribution boards and DB boxes where components sit on a DIN rail.

30 gDose
6Nozzle ports
12~15Coverage
Technical specification
Nozzle
6 ports
Shell resistance temp
250°C
Shell material
PA66-20
Coverage space
12 ~ 15 inches
Density
100 g/m³
Extinguishing dose
30 g
Trigger temp
≤ 170°C
Oxidizer agent
Sr(NO₃)₂ 60%, KNO₃ 20%
Technology
S-Type aerosol fire extinguishing
Working temp
−45°C ~ 90°C
Thermal spacing
0.3 m ≤ 75°C, 0.12 m ≤ 200°C
Wall-Mounted Type 10GWall-Mounted Type 10G - second view
PRODUCT 02

Wall-Mounted Type

Model 10G — A small wall-mounted unit for compact enclosures and panels.

10 gDose
2Nozzle ports
6~8Coverage
Technical specification
Nozzle
2 ports
Shell resistance temp
250°C
Shell material
PA66-20
Coverage space
6 ~ 8 inches
Density
100 g/m³
Extinguishing dose
10 g
Trigger temp
≤ 170°C
Oxidizer agent
Sr(NO₃)₂ 60%, KNO₃ 20%
Technology
S-Type aerosol fire extinguishing
Working temp
−45°C ~ 90°C
Thermal spacing
0.3 m ≤ 75°C, 0.12 m ≤ 200°C
Wall-Mounted Type 50GWall-Mounted Type 50G - second view
PRODUCT 03

Wall-Mounted Type

Model 50G — A larger wall-mounted unit for bigger cabinets and enclosed equipment spaces.

50 gDose
8Nozzle ports
20~26Coverage
Technical specification
Nozzle
8 ports
Shell resistance temp
250°C
Shell material
PA66-20
Coverage space
20 ~ 26 inches
Density
100 g/m³
Extinguishing dose
50 g
Trigger temp
≤ 170°C
Oxidizer agent
Sr(NO₃)₂ 60%, KNO₃ 20%
Technology
S-Type aerosol fire extinguishing
Working temp
−45°C ~ 90°C
Thermal spacing
0.3 m ≤ 75°C, 0.12 m ≤ 200°C
Lithium / Thermal-Runaway Type 60G QRRO 0.06G/S MC/FALithium / Thermal-Runaway Type 60G QRRO 0.06G/S MC/FA - second view
PRODUCT 04

Lithium / Thermal-Runaway Type

Model 60G QRRO 0.06G/S MC/FA — A stainless-steel thermal-runaway design for battery storage and lithium battery installations.

60 gDose
14Nozzle ports
200 g/m³Density
Technical specification
Nozzle
14 ports
Shell resistance temp
200°C
Shell material
Stainless steel
Coverage space
36 ~ 40 inches
Density
200 g/m³
Extinguishing dose
60 g
Trigger temp
≤ 175°C
Oxidizer agent
Sr(NO₃)₂ 50%, KNO₃ 10%
Technology
S-Type aerosol fire extinguishing
Working temp
−45°C ~ 90°C
Thermal spacing
0.3 m ≤ 75°C, 0.12 m ≤ 200°C
Stainless-Steel Shell Type 100G
PRODUCT 05

Stainless-Steel Shell Type

Model 100G — Our highest-capacity unit with a stainless-steel shell resistant up to 450°C.

100 gDose
16Nozzle ports
450°CShell temp
Technical specification
Nozzle
16 ports
Shell resistance temp
450°C
Shell material
Stainless steel
Coverage space
36 ~ 40 inches
Density
100 g/m³
Extinguishing dose
100 g
Trigger temp
≤ 170°C
Oxidizer agent
Sr(NO₃)₂ 60%, KNO₃ 20%
Technology
S-Type aerosol fire extinguishing
Working temp
−45°C ~ 90°C
Thermal spacing
0.3 m ≤ 75°C, 0.12 m ≤ 200°C

Compare

All models side by side

SpecificationDIN-RailWall 10GWall 50GLithiumSteel 100G
Nozzle6 ports2 ports8 ports14 ports16 ports
Shell resistance temp250°C250°C250°C200°C450°C
Shell materialPA66-20PA66-20PA66-20Stainless steelStainless steel
Coverage space12 ~ 15 inches6 ~ 8 inches20 ~ 26 inches36 ~ 40 inches36 ~ 40 inches
Density100 g/m³100 g/m³100 g/m³200 g/m³100 g/m³
Extinguishing dose30 g10 g50 g60 g100 g
Trigger temp≤ 170°C≤ 170°C≤ 170°C≤ 175°C≤ 170°C
Oxidizer agentSr(NO₃)₂ 60%, KNO₃ 20%Sr(NO₃)₂ 60%, KNO₃ 20%Sr(NO₃)₂ 60%, KNO₃ 20%Sr(NO₃)₂ 50%, KNO₃ 10%Sr(NO₃)₂ 60%, KNO₃ 20%
TechnologyS-Type aerosol fire extinguishingS-Type aerosol fire extinguishingS-Type aerosol fire extinguishingS-Type aerosol fire extinguishingS-Type aerosol fire extinguishing
Working temp−45°C ~ 90°C−45°C ~ 90°C−45°C ~ 90°C−45°C ~ 90°C−45°C ~ 90°C
Thermal spacing0.3 m ≤ 75°C, 0.12 m ≤ 200°C0.3 m ≤ 75°C, 0.12 m ≤ 200°C0.3 m ≤ 75°C, 0.12 m ≤ 200°C0.3 m ≤ 75°C, 0.12 m ≤ 200°C0.3 m ≤ 75°C, 0.12 m ≤ 200°C

Our innovations

Industry-focusedsafety technology

As Modern Safety Protection technologies advance, Aerosol Fire Suppression technology has evolved to its third generation. MAGIC is designed to chemically prevent and suppress fires — causing no harm to humans — before they escalate from the incipient stage to the growth stage.

01

Thermal activation

Aerosol systems typically trigger by thermal, electric or manual activation. MAGIC uses a heat-sensing system so no electrical power is needed.

02

Early intervention at 170°C

Before a fire progresses from the incipient to the growth stage, 170°C triggers the system, which releases the agent via a heat-sensing thermal cord.

03

Chemical principle

Fire needs heat, fuel, oxygen and a chemical chain reaction. MAGIC disrupts the chain reaction of H•, O• and OH• radicals within the flame.

Diagram: combustion reaction chain versus Sr particles interrupting the reaction chainClick to enlarge

Every space is different.

The MAGIC Safety team calculates your exact aerosol requirement using the NFPA 2010 standard.

Request a calculation