Optimized &industry-ready solutions
Five MAGIC models — from a 10 g wall-mounted unit to a 100 g stainless-steel version — all using S-Type aerosol fire extinguishing technology.


DIN-Rail Type
Model 30G — A compact unit for electrical cabinets, distribution boards and DB boxes where components sit on a DIN rail.
Technical specification
- Nozzle
- 6 ports
- Shell resistance temp
- 250°C
- Shell material
- PA66-20
- Coverage space
- 12 ~ 15 inches
- Density
- 100 g/m³
- Extinguishing dose
- 30 g
- Trigger temp
- ≤ 170°C
- Oxidizer agent
- Sr(NO₃)₂ 60%, KNO₃ 20%
- Technology
- S-Type aerosol fire extinguishing
- Working temp
- −45°C ~ 90°C
- Thermal spacing
- 0.3 m ≤ 75°C, 0.12 m ≤ 200°C


Wall-Mounted Type
Model 10G — A small wall-mounted unit for compact enclosures and panels.
Technical specification
- Nozzle
- 2 ports
- Shell resistance temp
- 250°C
- Shell material
- PA66-20
- Coverage space
- 6 ~ 8 inches
- Density
- 100 g/m³
- Extinguishing dose
- 10 g
- Trigger temp
- ≤ 170°C
- Oxidizer agent
- Sr(NO₃)₂ 60%, KNO₃ 20%
- Technology
- S-Type aerosol fire extinguishing
- Working temp
- −45°C ~ 90°C
- Thermal spacing
- 0.3 m ≤ 75°C, 0.12 m ≤ 200°C


Wall-Mounted Type
Model 50G — A larger wall-mounted unit for bigger cabinets and enclosed equipment spaces.
Technical specification
- Nozzle
- 8 ports
- Shell resistance temp
- 250°C
- Shell material
- PA66-20
- Coverage space
- 20 ~ 26 inches
- Density
- 100 g/m³
- Extinguishing dose
- 50 g
- Trigger temp
- ≤ 170°C
- Oxidizer agent
- Sr(NO₃)₂ 60%, KNO₃ 20%
- Technology
- S-Type aerosol fire extinguishing
- Working temp
- −45°C ~ 90°C
- Thermal spacing
- 0.3 m ≤ 75°C, 0.12 m ≤ 200°C


Lithium / Thermal-Runaway Type
Model 60G QRRO 0.06G/S MC/FA — A stainless-steel thermal-runaway design for battery storage and lithium battery installations.
Technical specification
- Nozzle
- 14 ports
- Shell resistance temp
- 200°C
- Shell material
- Stainless steel
- Coverage space
- 36 ~ 40 inches
- Density
- 200 g/m³
- Extinguishing dose
- 60 g
- Trigger temp
- ≤ 175°C
- Oxidizer agent
- Sr(NO₃)₂ 50%, KNO₃ 10%
- Technology
- S-Type aerosol fire extinguishing
- Working temp
- −45°C ~ 90°C
- Thermal spacing
- 0.3 m ≤ 75°C, 0.12 m ≤ 200°C

Stainless-Steel Shell Type
Model 100G — Our highest-capacity unit with a stainless-steel shell resistant up to 450°C.
Technical specification
- Nozzle
- 16 ports
- Shell resistance temp
- 450°C
- Shell material
- Stainless steel
- Coverage space
- 36 ~ 40 inches
- Density
- 100 g/m³
- Extinguishing dose
- 100 g
- Trigger temp
- ≤ 170°C
- Oxidizer agent
- Sr(NO₃)₂ 60%, KNO₃ 20%
- Technology
- S-Type aerosol fire extinguishing
- Working temp
- −45°C ~ 90°C
- Thermal spacing
- 0.3 m ≤ 75°C, 0.12 m ≤ 200°C
Compare
All models side by side
| Specification | DIN-Rail | Wall 10G | Wall 50G | Lithium | Steel 100G |
|---|---|---|---|---|---|
| Nozzle | 6 ports | 2 ports | 8 ports | 14 ports | 16 ports |
| Shell resistance temp | 250°C | 250°C | 250°C | 200°C | 450°C |
| Shell material | PA66-20 | PA66-20 | PA66-20 | Stainless steel | Stainless steel |
| Coverage space | 12 ~ 15 inches | 6 ~ 8 inches | 20 ~ 26 inches | 36 ~ 40 inches | 36 ~ 40 inches |
| Density | 100 g/m³ | 100 g/m³ | 100 g/m³ | 200 g/m³ | 100 g/m³ |
| Extinguishing dose | 30 g | 10 g | 50 g | 60 g | 100 g |
| Trigger temp | ≤ 170°C | ≤ 170°C | ≤ 170°C | ≤ 175°C | ≤ 170°C |
| Oxidizer agent | Sr(NO₃)₂ 60%, KNO₃ 20% | Sr(NO₃)₂ 60%, KNO₃ 20% | Sr(NO₃)₂ 60%, KNO₃ 20% | Sr(NO₃)₂ 50%, KNO₃ 10% | Sr(NO₃)₂ 60%, KNO₃ 20% |
| Technology | S-Type aerosol fire extinguishing | S-Type aerosol fire extinguishing | S-Type aerosol fire extinguishing | S-Type aerosol fire extinguishing | S-Type aerosol fire extinguishing |
| Working temp | −45°C ~ 90°C | −45°C ~ 90°C | −45°C ~ 90°C | −45°C ~ 90°C | −45°C ~ 90°C |
| Thermal spacing | 0.3 m ≤ 75°C, 0.12 m ≤ 200°C | 0.3 m ≤ 75°C, 0.12 m ≤ 200°C | 0.3 m ≤ 75°C, 0.12 m ≤ 200°C | 0.3 m ≤ 75°C, 0.12 m ≤ 200°C | 0.3 m ≤ 75°C, 0.12 m ≤ 200°C |
Specifications are published values. Please confirm the exact model, quantity and installation for your space with our team before purchase.
Our innovations
Industry-focusedsafety technology
As Modern Safety Protection technologies advance, Aerosol Fire Suppression technology has evolved to its third generation. MAGIC is designed to chemically prevent and suppress fires — causing no harm to humans — before they escalate from the incipient stage to the growth stage.
Thermal activation
Aerosol systems typically trigger by thermal, electric or manual activation. MAGIC uses a heat-sensing system so no electrical power is needed.
Early intervention at 170°C
Before a fire progresses from the incipient to the growth stage, 170°C triggers the system, which releases the agent via a heat-sensing thermal cord.
Chemical principle
Fire needs heat, fuel, oxygen and a chemical chain reaction. MAGIC disrupts the chain reaction of H•, O• and OH• radicals within the flame.
Click to enlargeEvery space is different.
The MAGIC Safety team calculates your exact aerosol requirement using the NFPA 2010 standard.
Request a calculation